Tuesday, September 10, 2019

Carbon Dioxide Fire Suppression System Essay Example | Topics and Well Written Essays - 250 words

Carbon Dioxide Fire Suppression System - Essay Example For carbon dioxide to be effective as a total flooding fire suppressant, a minimum design of 34% concentration is needed. However, laboratory testing and simulation of carbon dioxide fire suppressant use indicate that concentrations greater than 17% results to loss of controlled and purposeful activity, convulsions, unconsciousness, coma and even death within 1 minute of initial inhalation (OSHA, 1999). Even at 10-17% concentrations, carbon dioxide inhalation has been shown by Wong (1992) to result to drowsiness, sever muscle twitching and even unconsciousness. At 7 to 10 percent, headaches, visual and hearing dysfunction, hallucination and shortness of breath have been observed. At a minimum of 34% designed concentration for effectiveness, Carbon dioxide suppression systems are lethal. Any inadvertent discharge of the carbon dioxide in an occupied room can cause death quickly and without warning. The National Fire Protection Agency and the Occupational Safety and Health Authority have established guidelines such that human exposure do not occur during fire-fighting events but documented cases occurred during system installation, commissioning and maintenance because many of the servicemen lack the necessary knowledge and training. OSHA (1999) Carbon Dioxide, Industrial Exposure and Control Technologies for OSHA Regulated Hazardou

No comments:

Post a Comment

Note: Only a member of this blog may post a comment.